IHI Powersystems

start global navi.

グローバルメニューここまでです。

LM2500 Series

High efficiency and high reliability with aircraft engine technology

LM2500 Series models are two-shaft gas turbines for land and marine applications, derived from TF39 and CF6-50 model aircraft engines manufactured by General Electric (GE), an American company. IHI has built up a lot of experiences and a proven record in producing gas turbines for use in power generation, mechanical drive systems, and marine engines.

460*268


460*268



Product Features

Top-Class power generation efficiencies in the world
High reliability founded on abundant experiences in the field
Capability to start up and shut down gas turbine at rapid speed with aircraft engine technology
Dual-Fuel : Capability to use both gas fuels and liquid fuels
Capability to prepare and deliver gas turbine in short time
Availability of burners with low NOx emissions for selection
Light weight, compact size, and ease of maintenance

Product features

LM2500PJ performance

System type Simple cycle Combined heat and power (cogeneration)
Fuel City gas/Natural gas City gas/Natural gas
Frequency 50Hz 60Hz 50Hz 60Hz
Power output 21,170kW 22,100kW 20,530kW 21,460kW
Fuel consumption rate 10.37MJ/kWh 10.01MJ/kWh 10.32MJ/kWh 10.20MJ/kWh
Thermal efficiency at the generator terminal 34.7% 36.0% 34.9% 35.3%
Total thermal efficiency - - 85.9% 86.8%
NOx(O2=16%) 21ppm 21ppm

*Conditions
Inlet air temperature: 15℃
Atmospheric pressure: 101.3 kPa
Boiler supply water temperature: 60℃
*The above performance values list average performance in New & Clean mode.
*Note that the above performance values may be subject to change without prior notice.

Inlet air temperature

LM2500RD performance

System type Simple cycle Combined heat and power (cogeneration)
Fuel City gas/Natural gas City gas/Natural gas
Frequency 50Hz 60Hz 50Hz 60Hz
Power output 31,740kW 31,930kW 31,510kW 31,580kW
Fuel consumption rate 9.54 MJ/kWh 9.48 MJ/kWh 9.60 MJ/kWh 9.54 MJ/kWh
Thermal efficiency at the generator terminal 37.7% 38.0% 37.3% 37.7%
Total thermal efficiency - - 85.1% 86.1%
NOx(O2=16%) 21ppm 21ppm

*Conditions
Inlet air temperature: 15℃
Atmospheric pressure: 101.3 kPa
Boiler supply water temperature: 60℃
*The above performance values list average performance in New & Clean mode.
*Note that the above performance values may be subject to change without prior notice.

電端出力の吸湿度特性 燃料:灯油


Standard LM2500 Layout Diagram/Combined Heat and Power (Cogeneration)

Standard LM2500 Layout
Symbol Name
1 Gas turbine generator
2 Heat recovery steam generator
3 Gas filter unit for gas turbine fuel
4 Fuel gas compressor
5 Chemical dosing unit
6 Sampling unit
7 Supply water pump
8 Cooling water pump
9 Cooling tower
10 Air compressor for the instruments
11 Exhaust gas analyzer
12 Main transformer
13 Sub transformer
14 Motor transformer
15 Switch gear
16 High-voltage power receiving and transforming unit
17 1F Electrical room/2F Control room

Page Top